Allentown, PA- To explode, leaking natural gas needs to reach a concentration of 5 percent in the air.

Long before that, when it reaches 1 percent, you should be able to smell it and get out of the building.

At least that is how it is supposed to work.

Natural gas is odorless, but federal regulations require gas companies like UGI, or their suppliers, to inject enough odor that someone with a normal sense of smell can detect a leak when the gas hits one-fifth the concentration at which a spark can ignite it. Gas companies must make sure the gas they use, even if from a supplier, is properly odorized.

The rule was adopted after an instructor, oblivious to a gas leak in the crawl space of a New London, Texas, school building, turned on an electric sander and set off an explosion that killed 298 children and teachers in March 1937.

Seventy-four years later, despite the regulations that tragedy or inspired, no one reported smelling anything in the 1300 block of Allen Street in Allentown 16 months ago, when a leaking 12-inch cast-iron main allowed gas to build up, leading to a catastrophic explosion that killed five people and leveled eight rowhomes.

The disaster illustrates how one of the gas companies’ primary safety measures is far from foolproof.

“The gas companies know it, and in my opinion don’t take adequate precautions to protect the public,” said Paul R. Bladdick, a master plumber and owner of a Michigan consulting practice who has testified as an expert witness in cases involving gas safety.

To hold gas companies’ safety efforts accountable, the Pennsylvania Public Utility Commission and regulators in most other states rely on vague federal pipeline safety regulations that say little about how, when or where utilities verify odorant levels to ensure they are adequate to protect the public.

Federal law says only that gas companies must “conduct periodic sampling of combustible gases using an instrument capable of determining the percentage of gas in air at which the odor becomes readily detectable.”

In its complaint against UGI over the February 2011 explosion in Allentown, the PUC accused the company of violating even those limited requirements by failing to test odor levels throughout the city, performing weekly testing at only one location where gas enters the system.

At the beginning of this year, Allentown had more than 72 miles of cast-iron pipelines alone.

Of the 179 counts filed against UGI by the PUC, 156 involved failure to monitor odor levels.

In Louisiana, one of two states to significantly tighten odorant testing requirements beyond the federal rules, gas companies are required to test odorant levels “at the most remote locations in the system” and report the results at least once a quarter.

“That is just something they should be doing,” said Steven Giambrone, a petroleum analyst manager who handles pipeline safety for Louisiana. “Rather than leaving any doubt, it’s in there. That way you have to do it. You certainly would be wise to test at your furthest downstream point, that is the area you are going to see the least amount of odorant.”

Rather than stop at the broad guidelines laid out in federal law, Louisiana opted to incorporate best practices in the regulations to make sure safe odorant levels are maintained throughout the system, he said. The rules also set guidelines for odorization equipment and test locations.

“It is going to be stronger at the tap, where you are putting it in,” Giambrone said. “You are going to lose it at the walls of the pipe, you are going to have little leaks that aren’t major, you are going to lose a little bit there and just natural dissipation.”

Old, rusting pipelines like the distribution lines serving much of Allentown tend to absorb odorant, said Mark Gottlieb, a Philadelphia attorney who advocates for greater disclosure of the risk of so-called “odor fade.”

“It seems to me, if you are dealing with an older system, one of the ways you could be prophylactic would be by doing more spot testing at different points in the system,” he said.

The other state to tighten regulations, Arkansas, requires gas companies to test the strength of gas odorant “at the furthest points from the odorizer” at least once every three months.

The Pennsylvania Public Utility Commission has generally “been satisfied with the federal standards and the enforcement powers and opportunities that they provide us,” said spokeswoman Jennifer Kocher.

In its response to the PUC’s complaint over the February 2011 Allentown explosion, UGI said it “routinely monitors the gas in its distribution system to ensure proper odorization” and tested the gas across its Lehigh distribution area two days before the explosion and the day after, finding the odorant level met or exceeded requirements.

Trained UGI workers perform the testing to industry standards using an odorometer.

“Odorant testing is performed on varying schedules that range in frequency from weekly to monthly. UGI has 15 odorant testing points throughout UGI’s Lehigh Valley service territory,” the utility said in a statement provided The Morning Call.

Mark McDonald, president of the New England Gas Workers Association, said he suspects gas at the site of the Allentown gas leak was not properly odorized because when a main the size of the 12-inch cast-iron line that cracked in Allentown breaks, a lot of gas escapes.

“The odor is generally overwhelming,” he said. “In fact, many company first responders can diagnose a broken main the minute they exit their vehicle, simply from the widespread odor, which is usually called in by neighbors. To have no odor calls called in at this large break makes no sense unless the odorant was low.”

And McDonald said that because the PUC said UGI technicians who responded to the explosion tested odorant levels in the wrong, unrelated neighborhood gas line, it may never be known for sure. That mistake was cited by the PUC as a violation in its complaint against UGI, but the company has not acknowledged it.

There are other ways the odor can be stripped from natural gas. Gas that leaks through the ground can also be stripped of its odorant. It’s possible that the gas in the 12-inch cast-iron line running down Allen Street was properly odorized but lost its odor as the gas migrated from the street into the homes.

Newly installed plastic pipelines can absorb odorant if not properly treated before being put into use, experts say. And customers’ sense of smell varies greatly.

Based on the freezing conditions at the time of Allentown’s explosion, McDonald said he doubts the gas would have been stripped of all its odorant in the distance it traveled in the frozen ground from the distribution line to the houses.

Still, it’s a phenomenon most people don’t even know exists because gas companies don’t go out of their way to warn customers, said Barbrae Lundberg, a California attorney who has handled multiple cases involving natural gas explosions.

“They don’t want to talk about that, because it will scare people,” Lundberg said. “You have old gas lines all over this country.”

scott.kraus@mcall.com

610-820-6745

SMELL TEST

Pennsylvania pipeline safety regulators rely on federal safety guidelines to monitor natural gas utilities’ efforts to properly odorize their gas. Here are the primary requirements:

• A combustible gas in a distribution line must contain a natural odorant or be odorized so that at a concentration in air of one-fifth of the lower explosive limit, the gas is readily detectable by a person with a normal sense of smell.

• Equipment for odorization must introduce the odorant without wide variations in the level of odorant.

• Each operator must conduct periodic sampling of combustible gases using an instrument capable of determining the percentage of gas in air at which the odor becomes readily detectable.

•The odorant cannot be toxic when inhaled or corrosive or harmful to gas pipes, equipment and fittings. It cannot be deleterious to persons, materials or pipe. It cannot be water soluble to an extent greater than 2.5 parts per 100 by weight.

Source: Code of Federal Regulations